7-20
H Factory Tuning: C8
Para
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
C8-08
Speed
feedback
detection
control
(AFR) gain
Sets the gain and time constant
of the internal speed feedback
detection control circuit.
Normally it is not necessary to
set these parameters. Adjust in
the following circumstances:
0.00 to
10.00
1.00 NO X X A X 6-5
AFR Gain
ances:
S Hunting occurs:
Increase C8-09. If that does
C8-09
Speed
feedback
detection
control
(AFR) time
constant
not correct the problem,
reduce C8-08.
S Poor responsiveness:
Reduce C8-09 as long as
hunting does not occur
.
Increase the gain in C8-08
as long as hunting does not
0 to
2000
50 NO X X A X 6-5
AFR Time
occur.
Note
Unit for C8-09: ms
C8-30
Carrier
Frequency
Selection
During
Auto-tuning
Sets the carrier frequency
during Auto-tuning. Normally it
is not necessary to set this
parameter
. Adjust if auto-tuning
is not functioning.
0:
Sets the carrier frequency
to 2 kHz.
0 to 2
2 NO X X A A 6-8
Carrier in
tune
.
1:
Sets the carrier frequency
to the value in C6-01.
2:
Sets the carrier frequency
to 5 kHz.
Parameter Lists Chapter
7