7-19
H Carrier Frequency: C6
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
C6-01
Carrier
frequency
upper limit.
Sets the carrier frequency
upper limit and lower limit in
kHz units. (See note 2)
The carrier frequency
2.0
to
15.0
(see
note 1)
15.0
(see
note 1)
NO B B B B 6-62
Carrier
Freq Max
()
The carrier frequency
proportional gain is set as
follows:
(
note 1)
)
C6-02
Carrier
frequency
lower limit.
follows:
Note:
In vector control mode,
the upper limit of the car
-
rier frequency is fixed at
C6 01
0.4
to
15.0
(see
note 1)
15.0
(see
note 1)
NO A A X X 6-62
Carrier
Freq Min
qy
C6-01
Carrier frequency
(
note 1)
)
C6-03
Carrier
frequency
proportional
gain.
Output frequency × (C6-03)
× K
C6-01
C6-02
0
to 99
0 NO A A X X 6-62
Carrier
Freq Gain
Output frequency
(Max. frequency)
E1-04
0
Note 1. The
setting
range and the default of the Inverter will dif
fer depending on its capacity and con
-
trol
mode. (The value for the 200-V class 0.4 kW Inverter in open loop vector control mode is
given above.)
Note 2. For
a 400-V Inverter
, if the carrier frequency is set to a value higher than the default setting, the
Inverter overload “OL2” detection value will decrease.
H Hunting Prevention: C7
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
C7-01
Hunting
prevention
selection
0: Disabled
1: Enabled
Note:
The hunting prevention
function is used to stop a
motor under a light load
from hunting.
This function is exclusive-
ly for the V/f control
0, 1
1 NO A A X X 6-14,
6-38
Hunt Prev
Select
ly for the V/f control
mode.
When greater responsive
-
ness than vibration con
-
trol is required, set hunt
-
ing prevention to “dis
-
abled.”
C7-02
Hunting
prevention
gain
Sets the ratio for hunting
prevention gain.
Note:
Usually setting is not nec
-
essary.
Adjust in the following cir
-
cumstances:
When vibration occurs
due to a li
g
ht load
,
in
-
0.00 to
2.50
1.00 NO A A X X 6-14,
6-38
Hunt Prev
Gain
due
to
a
light
load
,
in
-
crease the set values.
When the motor is stalled,
decrease the set values.
If the set values become
too large, the motor may
stall as a result of non-
controlled current.
Parameter Lists Chapter
7