EasyManua.ls Logo

Omron SYSDRIVE 3G3MV SERIES - Page 151

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-9
Set Values
These parameters prevent the motor from over excitation due to voltage changes during energy-sav-
ing control.
Set the upper limit of output voltage in percentage at each frequency based on the rated motor voltage
as 100%.
Normally, the default settings do not need to be changed.
Output voltage
upper limit (%)
Output frequency (Hz)
n144
Probe Operation Voltage Limit Register 0190 Hex Changes during
operation
No
Setting
range
0 to 100 (%) Unit of
setting
1% Default setting 0
Set Values
When the output frequency is constant for a certain period while the Inverter is in effective energy-sav-
ing control, the Inverter will be set to the primary level of energy-saving control by n140 (energy-saving
constant K2). Then the Inverter will be set to the secondary level (i.e., probe operation) for more effi-
cient, energy-saving control. Set the control voltage range of the Inverter in probe operation in param-
eter n144.
Set the upper limit of probe operation voltage in percentage based on the rated motor voltage as
100%. Normally set the value to approximately 10%.
No probe operation will be available if the value is set to 0.
n145
Probe Operation Control Voltage
Step at 100%
Register 0191 Hex Changes during
operation
No
Setting
range
0.1 to 10.0 (%) Unit of
setting
0.1% Default setting 0.5
n146
Probe Operation Control Voltage
Step at 5%
Register 0192 Hex Changes during
operation
No
Setting
range
0.1 to 10.0 (%) Unit of
setting
0.1% Default setting 0.2
Advanced Operation Chapter 6

Table of Contents

Related product manuals