6-34
and capacity of the motor.) When setting the undertorque detection level, allow for a no-load cur-
rent.
n119
Undertorque detection time Register 0177 Hex Changes during
operation
No
Setting
range
0.1 to 10.0 (s) Unit of
setting
0.1 s Default setting 0.1 s
Set Values
Set the undertorque detection time.
The Inverter will detect undertorque when current (or torque) the same as or lower than the detection
level is output for the preset detection time.
Advanced Operation Chapter 6