10-13
Para
me-
ter
No.
Reg-
ister
No.
(Hex)
Name Description Set-
ting
range
Unit
of
set-
ting
Default
setting
Chan-
ges dur-
ing
opera-
tion
Ref-
er-
ence
page
27 Accelera-
tion/decel-
eration time
selection 2
A pair of inputs is
needed to select ac-
celeration and decel-
eration times.
If accel-
eration/deceleration
time selection 2 (set-
ting: 27) is not set at
any multi-function in-
put from n050 to n056,
the Inverter will deter-
mine that the accelera-
tion/deceleration
selection 2 is set to
OFF, and select the
acceleration/decelera-
tion time.
In the same way, if ac-
celeration/deceleration
time selection 1 (set-
ting: 11) is not set at
any multi-function in-
put, the Inverter will
determine that the ac-
celeration/deceleration
selection 1 is set to
OFF, and select the
acceleration/decelera-
tion time.
Selection
2
Selection
1
Acceleration/
deceleration time
Acceleration time 1 (n019)
Deceleration time 1 (n020)
Acceleration time 2 (n021)
Deceleration time 2 (n022)
Acceleration time 3 (n041)
Deceleration time 3 (n042)
Acceleration time 4 (n043)
Deceleration time 4 (n044)
OFF OFF
OFF ON
ON OFF
ON ON
List of Parameters Chapter 10