10-12
Para
me-
ter
No.
Ref-
er-
ence
page
Chan-
ges dur-
ing
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
DescriptionNameReg-
ister
No.
(Hex)
19 Emergency
stop fault
(NO)
The Inverter stops
according to the set-
ting in n005 for inter-
ruption mode selection
with the emergency
stop input turned ON
20 Emergency
stop warn-
ing (NO)
stop
i
nput turne
dON
.
NO: Emergency stop
with the contact
closed.
NC: Emergency stop
with the contact
21 Emergency
stop fault
(NC)
with the contact
opened.
Fault: Fault output is
ON and reset with
RESET input. Warning
out
p
ut is ON
(
no reset
22 Emergency
stop warn-
ing (NC)
output is ON (no reset
required).
“STP” is displayed (lit
with fault input ON and
flashes with alarm
input ON)
23 PID control
cancel
ON: PID control dis-
abled.
24 PID control
integral
reset
ON: Integral value
reset.
25 PID control
integral
hold
ON: Keeps integral
value on hold.
26
(See
note)
Inverter
overheating
warning
ON: Displays inverter
overheating warning
(oH3).
Note Inverter overheating warning (setting value: 26) can be set for 5.5-kW and 7.5-kW Inverters only.
List of Parameters Chapter 10