10-19
Para
me-
ter
No.
Reg-
ister
No.
(Hex)
Name Description Set-
ting
range
Unit
of
set-
ting
Defaul
t set-
ting
Chan-
ges dur-
ing
opera-
tion
Ref-
er-
ence
page
n066 0142 Multi-func-
tion analog
output
Selects the monitor item with n065 set to 0.
0: Output frequency (with 10-V output at max.
frequency)
1: Output current (with 10-V output with
Inverter rated output current)
2: Main circuit DC voltage (with 10-V output at
400 [800] V DC)
3: Vector operation torque monitor (with 10-V
output at rated motor torque)
4: Output power (with 10-V output at power
equivalent to max. applicable motor capac-
ity) Cannot be monitored in vector control
mode.
5: Output voltage (with 10-V output at
200 [400] V AC)
* Values in ( ) apply with n067 set to 1.00.
* Values in [ ] are for 400-V models.
0 to 5 1 0 No 5-38
n067 0143 Multi-func-
tion analog
output gain
Used to set the output characteristics of multi-
function analog output.
0.00
to
2.00
0.01 1.00 Yes 5-38
n068 0144 Multi-func-
tion analog
voltage
input gain
Sets the input characteristics of multi-function
analog voltage input.
Gain:Sets the frequency of maximum analog
input (10 V) in percentage based on the
–255
to 255
1% 100 Yes 5-16
n069 0145 Multi-func-
tion analog
voltage
input bias
input (10 V) in percentage based on the
maximum frequency as 100%.
Bias: Sets the frequency of minimum analog
input (0 V) in percentage based on the
maximum frequency as 100%.
–100
to 100
1% 0 Yes 5-16
n070 0146 Multi-func-
tion analog
voltage
input filter
time con-
stant
Sets a primary lag digital filter for multi-function
analog voltage input.
0.00
to
2.00
0.01 s 0.10 Yes 5-17
n071 0147 Multi-func-
tion analog
current
input gain
Sets the input characteristics of multi-function
analog current input.
Gain:Sets the frequency of maximum analog
input (20 mA) in percentage based on the
–255
to 255
1% 100 Yes 5-16
n072 0148 Multi-func-
tion analog
current
input bias
input (20 mA) in percentage based on the
maximum frequency as 100%.
Bias: Sets the frequency of minimum analog
input (4 mA) in percentage based on the
maximum frequency as 100%.
–100
to 100
1% 0 Yes 5-16
n073 0149 Multi-func-
tion analog
current
input filter
time con-
stant
Sets a primary delay digital filter for multi-func-
tion analog current input.
0.00
to
2.00
0.01 s 0.10 Yes 5-17
List of Parameters Chapter 10