EasyManua.ls Logo

Omron SYSDRIVE 3G3MV SERIES - Page 326

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-24
Para
me-
ter
No.
Reg-
ister
No.
(Hex)
Name Description Set-
ting
range
Unit
of
set-
ting
Defa
ult
set-
ting
Chan-
ges dur-
ing
opera-
tion
Ref-
er-
ence
page
n107 016B Motor
phase-to-
neutral
resistance
Set this parameter to the phase-to-neutral
resistance or 1/2 of the phase-to-phase resis-
tance of the motor.
* This parameter is used as a vector control
constant.
0.000
to
65.50
0.001
Ω
Varies
with
the
capac-
ity
No 5-5
6-2
n108 016C Motor leak-
age induc-
tance
Sets the leakage inductance of the motor in
use.
* This parameter is used as a vector control
constant.
* The Inverter with the default setting in this
parameter fully functions in vector control.
0.00
to
655.0
0.01
mH
Varies
with
the
capac-
ity.
No 6-2
n109 016D Torque
compensa-
tion limit
Sets a limit on the torque compensation func-
tion in vector control mode.
* Normally, the default setting does not need
to be changed.
* The Inverter in torque compensation control
limits the torque at a current 1.5 times larger
than the set value.
0 to
250
1% 150 No 6-3
n110 016E Motor no-
load cur-
rent
Used to set the no-load current of the motor in
use based on the rated motor current as 100%.
* Used as the constant of vector control and
the slip compensation function.
0 to
99
1% Varies
with
the
capac-
ity
No 5-6
n111 016F Slip com-
pensation
gain
Used to set the gain of the slip compensation
function.
* The default is set to 1.0 in vector control
mode.
* The slip compensation function is disabled
with n111 set to 0.0.
0.0 to
2.5
0.1 0.0 Yes 6-37
n112 0170 Slip com-
pensation
primary
delay time
Used for the response speed of the slip com-
pensation function.
* The default is set to 0.2 in vector control
mode.
* The default setting does not need any chan-
ges in normal operation.
0.0 to
25.5
0.1 s 2.0 No 6-37
n113 0171 Slip com-
pensation
during
regenera-
tion
Selects the slip compensation function in
regenerative operation.
0: Disabled
1: Enabled
* This parameter is valid only in vector control
mode.
0, 1 1 0 No 6-38
n114 Not used --- --- --- --- --- ---
List of Parameters Chapter 10

Table of Contents

Related product manuals