10-23
Para
me-
ter
No.
Ref-
er-
ence
page
Chan-
ges dur-
ing
opera-
tion
Defa
ult
set-
ting
Unit
of
set-
ting
Set-
ting
range
DescriptionNameReg-
ister
No.
(Hex)
n098 0162 Overtorque
detection
level
Used to set overtorque detection level.
Detection from output torque: Set as a percent-
age based on the rated motor torque as 100%.
Detection from output current: Set as a per-
centage based on the rated Inverter output cur-
rent as 100%.
30 to
200
1% 160 No 6-32
n099 0163 Overtorque
detection
time
Used to set the detection time for overtorque. 0.1 to
10.0
0.1 s 0.1 No 6-32
n100 0164 UP/DOWN
frequency
memory
Used to store the adjusted frequency reference
with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or
more.
0, 1 1 0 No 6-45
n101 0165 Speed
search de-
celeration
time (See
note.)
Sets the speed search deceleration time as the
time required to go from 100% to 0% of the
maximum frequency.
This is a constant for adjusting the speed
search function. If “0.0” is set, the Inverter will
operate at the default time of 2.0 seconds.
0.0 to
10.0
0.1 s 2.0 No 5-35
n102 0166 Speed
search op-
erating lev-
el (See
note.)
Sets the speed search operating level as a
percentage, taking the Inverter’s rated output
current as 100%.
This is a constant for adjusting the speed
search function. If the Inverter output current
falls below the set value, the speed search will
be judged as completed and acceleration will
begin again.
0 to
200
1 % 150 No 5-35
n103 0167 Torque
compensa-
tion gain
Used to set the gain of the torque compensa-
tion function.
* The default setting does not need any chan-
ges in normal operation.
0.0 to
2.5
0.1 1.0 Yes 6-35
n104 0168 Torque
compensa-
tion pri-
mary delay
time con-
stant
Sets the response speed of the torque com-
pensation function.
* Normally, the default setting does not need
to be changed.
0.0 to
25.5
0.1 s 0.3 No 6-35
n105 0169 Torque
compensa-
tion core
loss
Sets the core loss of the motor in use.
* Normally, the default setting does not need
to be changed.
* This parameter is enabled in V/f control
mode only.
0.0 to
6,550
0.1 W Varies
with
the
capac-
ity.
No 6-35
n106 016A Rated
motor slip
Used to set the rated slip value of the motor in
use.
* Used as the constant of the slip compensa-
tion function or vector control.
0.0 to
20.0
0.1
Hz
Varies
with
the
capac-
ity.
Yes 6-37
Note Speed search deceleration time and speed search operating level can be set for 5.5-kW and
7.5-kW Inverters only.
List of Parameters Chapter 10