EasyManua.ls Logo

Omron SYSDRIVE 3G3MV SERIES - Page 50

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-18
D Selecting RS-422/485 Termination Resistance
Termination resistance can be selected by setting pin 1 of the SW2 to ON. The default setting for the
pin is OFF.
Selects RS-422/485 termination resistance
Selects frequency reference input method
Communications method Pin 1 setting
RS-422 Set to ON
RS-485 Set to ON only if the Unit is the end Slave.
120-Ω termination resistance (1/2 W)
Pin 1
D Selecting Frequency Reference Input Method
By using pin 2 of SW2, voltage input or current input can be selected as the input method for frequency
reference. The default setting is for voltage input.
Parameter settings are required together with the selection of the frequency reference input method.
Frequency reference input
method
Pin 2 setting Frequency reference selection
(parameter n004)
Voltage input (default setting) V (OFF) Set value 2
Current input I (ON) Set value 3 or 4
Note Do not set pin 2 to ON for current input while voltage is being input, otherwise the resistor in the
input circuit may burn out.
D Frequency Reference Input by Pulse Train Input
The RP terminal can input or output a PLC or external pulse generator signal directly to the Inverter if
an analog signal is unable to provide an accurate reference.
This allows speed ratio and tracking operation between inverters.
Pulse train
Input
Output
Pulse train
Input
Design Chapter 2

Table of Contents

Related product manuals