No. Description Unit Default Settings
− Model VZA − 22P2 24P0 25P5
C6-01 Normal/Heavy Duty − HD ND HD ND HD ND
o2-04 Drive Model Selection Hex 66 68 6A
E2-11
(E4-11,
T1-02)
Motor rated power kW 2.2 3.0 3.7 5.5 5.5 7.5
b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy saving coefficient − 156.8 136.4 122.9 94.75 94.75 72.69
C6-02 Carrier frequency − 3 7 3 7 3 7
E2-01
(E4-01,
T1-04)
Motor rated current A 8.5 11.4 14 19.6 19.6 26.6
E2-02
(E4-02)
Motor rated slip Hz 2.9 2.7 2.73 1.5 1.5 1.3
E2-03
(E4-03)
Motor no-load current A 3.0 3.7 4.5 5.1 5.1 8.0
E2-05
(E4-05)
Motor line-to-line resistance Ω 1.601 1.034 0.771 0.399 0.399 0.288
E2-06
(E4-06)
Motor leakage inductance % 18.4 19 19.6 18.2 18.2 15.5
E2-10
(E4-10)
Motor Iron Loss W 77 91 112 172 172 262
E5-01 Motor Code hex 0006 0006 0008 0008 FFFF FFFF
L2-02
Momentary power loss ride-
through time
s 0.5 0.5 1 1 1.0 1.0
L2-03
Momentary power loss Baseblock
time
s 0.5 0.5 0.6 0.7 0.7 0.8
L2-04
Momentary power loss voltage
recovery time
s 0.3 0.3 0.3 0.3 0.3 0.3
L2-05 Uv detection voltage V dc 190 190 190 190 190 190
L3-24 Motor acceleration time s 0.145 0.145 0.154 0.168 0.168 0.175
L8-02 Overheat alarm level °C 100 100 110 110 115 115
L8-09 Ground fault selection − 0 0 0 0 1 1
L8–35 Installation Method Sel. − 0 0 0 0 2 2
L8-38
Carrier frequency reduction
selection
− 1 1 1 1 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10
B.5 Defaults by Drive Capacity (o2-04) and ND/HD (C6-01)