Reviewing Power Requirements
High Voltage Three Phase (4W+GND) Comments
Amps per PDU 109A (6 inputs x 18.1A)
Outlets 42 C13
6 C19
Number of inputs 2 inputs x25A plug, 3 ph (4W+GND) 2 inputs/plugs per PDU, or 4 total inputs/
plugs for system
Input current 18 A max. per phase
Data center receptacle IEC 309-4P5W-IP44 (32A, 400V, AC, 3Ph)
Outlet groups per PDU 6
Usable PDU power cord length 2 m (6.6 feet) PDU power cords are 4 m long (13 feet), but
sections are used for internal routing in the
rack.
Summary:
Number of PDUs in Oracle SuperCluster T5-8: 2
Number of circuits per PDU: 2 @ 25A 3-phase 230/400V
Total number of circuits required: 4 @ 25A 3-phase 230/400V (2 per PDU)
Total number of data center receptacles required: 4 x IEC 309-4P5W-IP44
Total Amps per PDU: 109A 3-phase 230/400V
Total Amps for entire Oracle SuperCluster T5-8: 218A 3-phase 230/400V (2 PDUs @ 109A 3-phase 230/400V each)
Related Information
■
“Facility Power Requirements” on page 100
■
“PDU Thresholds” on page 104
■
“Power Consumption” on page 99
PDU Thresholds
This section provides the default PDU current thresholds for warnings and alarms for the
different SuperCluster T5-8 configurations.
You can also view the values by accessing the PDU metering unit as described in the Sun Rack
II Power Distribution Units User's Guide.
View the PDU thresholds and alarm values based on the configuration of SuperCluster T5-8:
■
“PDU Thresholds (Quarter-Populated Racks)” on page 105
■
“PDU Thresholds (Half-Populated Racks)” on page 105
■
“PDU Thresholds (Fully-Populated Racks)” on page 106
104 Oracle SuperCluster T5-8 Owner's Guide • May 2016