Reviewing Power Requirements
Reviewing Power Requirements
“Power Consumption” on page 99
“Facility Power Requirements” on page 100
“Grounding Requirements” on page 100
“PDU Power Requirements” on page 101
“PDU Thresholds” on page 104
Power Consumption
These tables describe power consumption of SuperCluster T5-8 and expansion racks.
These are measured values and not the rated power for the rack. For rated power specifications,
see “PDU Power Requirements” on page 101.
TABLE 4
SuperCluster T5-8
Condition Full Rack Half Rack
Maximum
Typical
15.97 kVA
15.17 kW
13.31 kVA
12.64 kW
9.09 kVA
8.6 kW
7.5 kVA
7.13 kW
TABLE 5
Exadata X5-2 Expansion Rack
Product Condition kW kVA
Extreme Flash quarter rack Maximum
Typical
3.6
2.5
3.7
2.6
High capacity quarter rack Maximum
Typical
3.4
2.4
3.4
2.4
Individual Extreme Flash storage server Maximum
Typical
.6
.4
.6
.4
Individual High capacity storage server Maximum
Typical
.5
.4
.5
.4
Preparing the Site 99

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle SuperCluster T5-8 and is the answer not in the manual?

Oracle SuperCluster T5-8 Specifications

General IconGeneral
BrandOracle
ModelSuperCluster T5-8
CategoryServer
LanguageEnglish

Related product manuals