Preparing for Installation
High Voltage Single Phase Comments
Usable PDU power cord length 2 m (6.6 feet) PDU power cords are 4 m long (13 feet), but
sections are used for internal routing in the
rack.
Related Information
“Facility Power Requirements” on page 100
“Grounding Requirements” on page 100
“System Power Consumption” on page 290
Preparing for Cooling
“Environmental Requirements” on page 293
“Heat Dissipation and Airflow Requirements” on page 294
“Perforated Floor Tiles” on page 296
Environmental Requirements
The following table lists temperature, humidity and altitude requirements.
TABLE 65
Temperature, Humidity, and Altitude
Condition Operating Requirement Non-operating Requirement Comments
Temperature 5 to 32°C (41 to 89.6°F) -40 to 70°C (-40 to 158°F). For optimal rack cooling, data
center temperatures from 21 to
23°C (70 to 47°F)
Relative humidity 10 to 90% relative humidity,
noncondensing
Up to 93% relative humidity. For optimal data center
rack cooling, 45 to 50%,
noncondensing
Altitude 3048 m (10000 ft.) maximum 12000 m (40000 ft.). Ambient temperature is reduced
by 1 degree Celsius per 300 m
above 900 m altitude above sea
level
Related Information
“Heat Dissipation and Airflow Requirements” on page 294
“Perforated Floor Tiles” on page 296
Connecting Expansion Racks 293

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle SuperCluster T5-8 and is the answer not in the manual?

Oracle SuperCluster T5-8 Specifications

General IconGeneral
BrandOracle
ModelSuperCluster T5-8
CategoryServer
LanguageEnglish

Related product manuals