Preparing for Installation
System Power Consumption
TABLE 59
Oracle Exadata Storage Expansion Rack Power Consumption
Comments Full Rack Half Rack Quarter Rack
Maximum
Typical
12.6 kW
12.9 kVA
8.8 kW
9.0 kVA
6.9 kW
7.1 kVA
4.8 kW
5.0 kVA
3.4 kW
3.5 kVA
2.4 kW
2.5kVA
Related Information
“PDU Power Requirements” on page 290
“Grounding Requirements” on page 100
“Facility Power Requirements” on page 100
PDU Power Requirements
When ordering the Oracle Exadata Storage Expansion Rack, you must provide two
specifications:
Low or high voltage
Single or three phase power
Refer to the following tables for Oracle marketing and manufacturing part numbers.
Note - Each Oracle Exadata Storage Expansion Rack has two power distribution units (PDUs).
Both PDUs in a rack must be the same type.
TABLE 60
PDU Choices
Voltage Phases Reference
Low 1 Table 61, “Low Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack,” on
page 291
Low 3 Table 62, “Low Voltage 3 Phase PDUs for Oracle Exadata Storage Expansion Rack,” on
page 291
High 1 Table 63, “High Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack,” on
page 292
290 Oracle SuperCluster T5-8 Owner's Guide • May 2016

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle SuperCluster T5-8 and is the answer not in the manual?

Oracle SuperCluster T5-8 Specifications

General IconGeneral
BrandOracle
ModelSuperCluster T5-8
CategoryServer
LanguageEnglish

Related product manuals