Preparing for Installation
High Voltage Three Phase Comments
Usable PDU power cord length 2 m (6.6 feet) PDU power cords are 4 m long (13 feet), but
sections are used for internal routing in the
rack.
TABLE 63
High Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack
High Voltage Single Phase Comments
kVA Size 15 kVA
Marketing part number N/A
Manufacturing part number N/A
Phase 1 ph
Voltage 220 to 240 VAC
Amps per PDU 72 A (3 inputs x24 A)
Outlets 42 C13
6 C19
Number of inputs 6
Input current 25 A max. per input
Data center receptacle IEC 60309 32A 3-pin 250VAC IP44
Outlet groups per PDU 6
Usable PDU power cord length 2 m (6.6 feet) PDU power cords are 4 m long (13 feet), but
sections are used for internal routing in the
rack.
TABLE 64
High Voltage 3 Phase PDUs for Oracle Exadata Storage Expansion Rack
High Voltage Single Phase Comments
kVA size 14.4 kVA
Marketing part number N/A
Manufacturing part number N/A
Phase 3 ph
Voltage 220/380 to 240/415 VAC
Amps per PDU 62.7 A (3 inputs x 20.9. A)
Outlets 42 C13
6 C19
Number of inputs 2 inputs x 25 A
Input current 25 A max. per phase
Data center receptacle IEC 60309 32A, 5-pin 230/400 VAC
Outlet groups per PDU 6
292 Oracle SuperCluster T5-8 Owner's Guide • May 2016