EasyManuals Logo

Oracle SuperCluster T5-8 User Manual

Oracle SuperCluster T5-8
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
Power On the System
7.
Secure the power cords in bundles.
8.
Connect the PDU power cord connectors into the facility receptacles.
Power On the System
1.
Ensure that each of the main power cords is connected.
2.
Turn on the facilities circuit breakers.
3.
Switch on power distribution unit B (PDU B) only.
Note - Do not turn on PDU A at this time.
PDU B is located on the right side of the rear of the rack. See below.
Press the ON (|) side of the toggle switches on PDU B.
130 Oracle SuperCluster T5-8 Owner's Guide • May 2016

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Oracle SuperCluster T5-8 and is the answer not in the manual?

Oracle SuperCluster T5-8 Specifications

General IconGeneral
BrandOracle
ModelSuperCluster T5-8
CategoryServer
LanguageEnglish

Related product manuals