Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL 9785 RFL Electronics Inc.
July 26, 2007
16-21 (973) 334-3100
16.6.3.2 DISPLAYING PARAMETER SETTINGS
To view a list of all current parameter settings, use the “D” command.
Format: 9785CB-P>D [ENTER]
When you enter the “D” command, the Checkback Module sends a list of all current parameter settings
to your terminal. Typical parameter setting lists for the two Checkback Module configuration modes
available when installed in an RFL 9785 (Master and Remote) are shown in Figures 16-16 and 16-17.
The following parameters appear on each parameter setting list:
999 - System Label
This is a user-defined identifier that appears on the second line of the APRIL command list. It
can be any combination of letters or numbers up to 30 characters long. It is normally used to
indicate a substation name, a line number, or some other identifier.
020 - Mode
This parameter sets the configuration mode for the checkback module being programmed. Two
settings are possible when the Checkback Module is installed in an RFL 9785: M (Master) and
R (Remote). The Checkback Module’s other two configuration modes (Head Slave and Slave)
cannot be used when it is installed in an RFL 9785.
021 - Slave Number (Slave only)
This parameter is only used at Slave checkback modules. Since Parameter #20 (Mode) can only
be set to “M” or “R” at Checkback Modules installed in an RFL 9785, this parameter is
automatically set to “N/A.”
022 - Hard Tx 1
This parameter selects the code that will be transmitted if the HC1 switch on the front panel is
pressed and held for five seconds (Hard Carrier 1).
023 - Hard Tx 2
This parameter selects the code that will be transmitted if the HC2 switch on the front panel is
pressed and held for five seconds (Hard Carrier 2).
024 - Hard Tx 3
This parameter selects the code that will be transmitted if the HC3 switch on the front panel is
pressed and held for five seconds (Hard Carrier 3).
025 - Hard Tx 4
This parameter selects the code that will be transmitted if the HC4 switch on the front panel is
pressed and held for five seconds (Hard Carrier 4).
026 - Low Rx HC
This parameter selects the received code that will cause the local terminal to respond with a
low-level hard carrier.