14.6.4 DISPLAYING AND EDITING PARAMETER SETTINGS
To view a list of all current parameter settings, use the “D” command.
9785-P>D [ENTER]
When you invoke the “D” command, the RFL 9785 sends a list of all current parameter settings to
your terminal. A typical parameter settings display is shown in Figure 14-6.
# PARAMETER SETTING
999 System Label
051 Time 16:14:07
052 Date 05/26/1999
053 Freq Ch1 (Hz) 170000
054 X Hybrid Ch1 N
055 Freq Ch2 (Hz) 170000
056 X Hybrid Ch2 N
9785-P>
Figure 14-6. Typical parameter settings display
To re-program any of the values shown on the parameter settings displays, type in the number in the
“#” column, and then press [ENTER]. The parameter will be displayed, with information about its
setting below it. Type in the new setting, and then press [ENTER].
Example 1: Editing the system time and date parameter settings.
If your RFL 9785 is connected to an IRIG-B generator, its system clock is being automatically
synchronized to the IRIG-B time clock, and no manual setting is required except for year. If you are
not using an IRIG-B generator, use the following procedure to set the RFL 9785’s system clock (note
that the time and date values entered will not take effect until stored using the “SV” command):
Enter the number for the Date parameter (52) on your terminal or PC keyboard, and then press the
[ENTER] key.
The Date parameter will be displayed, with information about its setting below it.
052 Date 05/24/1999
[mm/dd/(yy)yy]> _
Type in the current date (in “mm/dd/(yy)yy format), and then press the [ENTER] key.
The Year parameter will be re-displayed, set to the new value.
052 Date 05/25/1999
IRIG-B values will override entry here
Note the message that the IRIG-B input can override the manually entered date (other than
year, which is not a part of the IRIG-B data).
RFL 9785 RFL Electronics Inc.
April 25, 2005
14-8 (973) 334-3100