Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL 9785 RFL Electronics Inc.
June 18, 2009
18-3 (973) 334-3100
Output Over Current Protection:
+5.00Vdc 1.0 Amp foldback to 50% Max Load Current (500mA)
+/- 15Vdc Internal regulator @ 1.8 Amp foldback/Thermal
+12 Vdc Internal regulator @ 1.8 Amp foldback/Thermal
Output Ripple Voltage: Measured differentially with full load @ 150Vdc input
+5.00Vdc <200 mv pp
+15.0 Vdc <1200 mv pp
-15.0 Vdc <1200 mv pp
+12.0Vdc <1200 mv pp
Input Overvoltage Protection:
184 Vdc minimum (38 Vdc to 150 Vdc supply)
388 Vdc minimum (200 Vdc to 300 Vdc supply)
Isolation: As specified in ANSI/IEEE C37.90
3000Vdc Input to Output
3000Vdc Input to Chassis
Surge Withstand Requirements: As specified in ANSI/IEEE C37.90.1
The Power Supply input passes Oscillatory and Fast Transient SWC tests with no impact on
power supply outputs.
Environmental Specifications:
Temp Range -20
o
C to +60
o
C Still Air
Humidity 95% @ 40
o
C
Indicators:
DS1 – Normal Green

Table of Contents