124 Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 5 Connecting the Kinetix 6000 Drive System
When connecting 2094-BM03-x and 2094-BM05-x (double-wide) axis modules,
use 2090-SCEP0-2, 0.2 m (7.0 in.) cables. When connecting 2094-AMxx-x,
2094-BMP5-x, 2094-BM01-xM, and 2094-BM02-x (single-wide) axis modules,
use 2090-SCEP0-1, 0.1 m (5.1 in.) cables.
Figure 73 - Fiber-optic Cable Example - Logix Platform with Double-wide Modules
In this example, the second Kinetix 6000 system is located in a separate cabinet
and connected with bulkhead adapters.
Figure 74 - Fiber-optic Cable Example - Logix Platform with Bulkhead Adapters
SERCOS interface
TM
Tx (rear)
Rx (front)
OK
CP
0.1 m
(5.1 in.)
0.2 m
(7.1 in.)
1756-M16SE SERCOS
Interface Module
SERCOS Fiber-optic Ring
Kinetix 6000 System
(5-axis power rail)
Logix Platform
(ControlLogix is shown)
To avoid signal loss, do not use bulkhead adapters to connect glass
cables. Use only bulkhead adapters for making plastic-to-plastic cable
connections.
SERCOS interface
TM
Tx (rear)
Rx (front)
OK
CP
1756-MxxSE SERCOS
Interface Module
SERCOS Fiber-optic
Bulkhead Adapter
SERCOS Fiber-optic Ring
SERCOS Ring
SERCOS Fiber-optic
Bulkhead Adapter
Kinetix 6000
System
Kinetix 6000
System
Logix Platform
(ControlLogix is shown)
Transmit
Receive
Transmit
Receive
Receive
Transmit
Cabinet