EasyManua.ls Logo

Rockwell Automation Allen-Bradley 2094-BM01-S - Bonding Multiple Subpanels

Rockwell Automation Allen-Bradley 2094-BM01-S
280 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 2094-UM001D-EN-P - May 2010 33
Planning the Kinetix 6000 Drive System Installation Chapter 2
Bonding Multiple Subpanels
Bonding multiple subpanels creates a common low impedance exit path for the
high frequency energy inside the cabinet. Subpanels that are not bonded together
may not share a common low impedance path. This difference in impedance may
affect networks and other devices that span multiple panels.
Bond the top and bottom of each subpanel to the cabinet by using
25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) wire braid. As a rule, the wider
and shorter the braid is, the better the bond.
Scrape the paint from around each fastener to maximize metal-to-metal
contact.
Figure 8 - Multiple Subpanels and Cabinet Recommendations
Wire Braid
25.4 mm (1.0 in.) by
6.35 mm (0.25 in.)
Paint removed
from cabinet.
Cabinet ground bus
bonded to the subpanel.
Wire Braid
25.4 mm (1.0 in.) by
6.35 mm (0.25 in.)

Table of Contents