66 Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 4 Kinetix 6000 Connector Data
Contactor Enable Relay
Contactor enable is a relay-driven contact used in the safety control string to
protect the drive electronics during certain fault conditions. It is capable of
handling 120V AC or 24V DC at 1 A or less. Contactor enable is a function of
the converter and is not available in the axis modules. An active state indicates the
drive is operational and does not have a fault.
Figure 30 - Contactor Enable Relay Circuit
Table 32 - Contactor Enable Relay Output Specifications
ATTENTION: Wiring the contactor enable relay is required. To avoid
personal injury or damage to the drive, wire the contactor enable relay
into your safety control string so that:
three-phase power is removed from the drive in the event of shutdown
fault conditions.
drive operation is prevented when the power rail is not fully populated.
control power is applied to the drive prior to three-phase power.
Refer to IAM Module (without LIM module) on page 204
for a wiring
example.
IMPORTANT
All power rail slots must have a module installed or the contactor enable
relay will not close.
CONT EN-
CONT EN+
Normally
Open
Relay
Kinetix 6000
IAM Module
Attribute Value Min Max
On-state
current
Current flow when the relay is closed 1 A
On-state
resistance
Contact resistance when the relay is closed 1 Ω
Off-state
voltage
Voltage across the contacts when the relay is open
120V AC or
24V DC