Rockwell Automation Publication 2094-UM001D-EN-P - May 2010 99
Connecting the Kinetix 6000 Drive System Chapter 5
Wire the Motor Power (MP) Connector
Connections to the motor power (MP) connector include rotary motors, linear
motors, and motor driven actuators.
This example applies to AM modules and the inverter section of IAM modules.
Figure 51 - IAM/AM Module (MP connector)
Cable Shield Terminations
Factory-supplied Bulletin 2090 motor power cables for motors and acutators are
shielded, and the braided cable shield must terminate at the drive during
installation. A small portion of the cable jacket must be removed to expose the
shield braid. The exposed area must be clamped (with the clamp provided) on
top of the IAM or AM modules and the power wires terminated in the motor
power (MP) connector plug.
ATTENTION: Make sure the motor power connections are correct when
wiring the MP connector plug and that the plug is fully engaged in the
module connector. Incorrect wiring/polarity or loose wiring can cause
explosion or damage to equipment.
W
V
U
1 2 3 4
Cable Shield Clamp
Kinetix 6000
IAM/AM Module
(IAM module is shown)
SHOCK HAZARD: To avoid hazard of electrical shock, make sure
shielded power cables are grounded at a minimum of one point for safety.
IMPORTANT
For TL-Series motors, also connect the 152 mm (6.0 in.) termination wire
to the closest earth ground.
Refer to Pigtail Terminations on page 100
for more information.