30 Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 2 Planning the Kinetix 6000 Drive System Installation
Minimum Clearance Requirements
This section provides information to assist you in sizing your cabinet and
positioning your Bulletin 2094 system components.
Figure 6 - Minimum Clearance Requirements
(1) The power rail (slim), catalog number 2094-PRSx, extends left and right of the first and last module 5.0 mm
(0.20 in.). The power rail, catalog number 2094-PRx, extends approximately 25.4 mm (1.0 in.) left of the IAM
module and right of the last module mounted on the rail.
Table 8 - Minimum Clearance Dimensions
Refer to page 189 for power dissipation specifications.
Mount the module in an upright position. Do not mount the module on its
side.
Clearance right of the
module is not required.
(1)
Clearance above
for airflow and installation.
Clearance left of the
module is not required.
(1)
Kinetix 6000 IAM Module
(2094-BC01-Mxx-x is shown
mounted on power rail)
Power Rail
(2094-PRSx is shown)
Clearance below
for airflow and installation.
Cat. No. Clearance Above, Min Clearance Below, Min Cabinet Depth Clearance, Min
2094-AC05-Mxx-x, 2094-AC09-M02-x,
2094-AMP5-x, 2094-AM01-x, 2094-AM02-x
50.8 mm (2.0 in.) 50.8 mm (2.0 in.) 198 mm (7.8 in.)
2094-BC01-Mxx-x, 2094-BC02-M02-x,
2094-BMP5-x, 2094-BM01-x, 2094-BM02-x
50.8 mm (2.0 in.) 50.8 mm (2.0 in.)
272 mm (10.7 in.)
2094-BSP2 272 mm (10.7 in.)
2094-AC16-M03-x, 2094-AC32-M05-x,
2094-AM03-x, 2094-AM05-x
305 mm (12.0 in.) 50.8 mm (2.0 in.) 198 mm (7.8 in.)
2094-BC04-M03-x, 2094-BC07-M05-x,
2094-BM03-x, 2094-BM05-x
305 mm (12.0 in.) 50.8 mm (2.0 in.) 272 mm (10.7 in.)
Although clearance left and right of the power rail is not necessary for
ventilation, additional clearance is required when mounted adjacent to
noise sensitive equipment or clean wireways.