Rockwell Automation Publication 2094-UM001D-EN-P - May 2010 97
Connecting the Kinetix 6000 Drive System Chapter 5
Wire the Contactor Enable (CED) Connector
This example applies to any IAM, common-bus leader IAM, or common-bus
follower IAM module.
Figure 49 - IAM Module (CED connector)
Table 56 - Contactor Enable (CED) Connector
CONT EN-
CONT EN+
1 2
Kinetix 6000
IAM Module, Top View
ATTENTION: Wiring the contactor enable relay is required. To avoid
personal injury or damage to the drive, wire the contactor enable relay
into your safety control string. Refer to Contactor Enable Relay on
page 66
.
In common-bus configurations, the contactor enable (CED) connections for
leader and follower drives must be wired in series to the safety control
string.
For interconnect diagrams, refer to Interconnect Diagram Notes beginning
on page 200
.
LIM Module I/O (IOL) Connector or Other Control String
CED Pin Signal
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
2094-ALxxS, 2094-BLxxS, or
2094-XL75S-Cx LIM Modules
2094-AL09 and 2094-BL02
LIM Modules
IO_COM1 IO_COM 1 CONT EN-
2.5 (14)
(1)
10 (0.38)
0.5…0.6
(4.4…5.3)
COIL_E2 COIL_A2 2 CONT EN+
(1) The actual gauge of the contactor enable wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local codes.