Rockwell Automation Publication 2094-UM001D-EN-P - May 2010 39
Planning the Kinetix 6000 Drive System Installation Chapter 2
Observe these guidelines when the 2094-AL09 or 2094-BL02 LIM module is
used in the Bulletin 2094 system and mounted above the IAM module:
The clean zone (C) is to the right and beneath the Bulletin 2094 system
(gray wireway).
The dirty zone (D) is to the left and above the Bulletin 2094 system, and
above and below the LIM module (black wireway).
The LIM VAC output is very dirty (VD). Use shielded cable with a braid
clamp attached at both ends of the cable to reduce the rating to dirty (D).
The SERCOS fiber-optic cables are immune to electrical noise, but due to
their delicate nature, route them in the clean zone.
Figure 14 - Noise Zones (LIM mounted above IAM module)
(1) For examples of shield clamp attachment, refer to the System Design for Control of Electrical Noise Reference
Manual, publication GMC-RM001
.
(2) If drive system I/O cable contains (dirty) relay wires, route cable in dirty wireway.
(3) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For
examples, refer to the System Design for Control of Electrical Noise Reference Manual, publication
GMC-RM001
.
VD
D
D
D
D
C
C
C
Line Interface Module
Kinetix 6000
System
Dirty Wireway Clean Wireway
Motor Power Cables
Very dirty LIM/IAM
(1)
connections must be
shielded with braid
clamp at both ends.
I/O
(2)
and Feedback Cables
No sensitive
(3)
equipment within
150 mm (6.0 in.).
Route 24V DC I/O
shielded cable.
Route encoder/analog/registration
shielded cables.
Fiber-optic Cable