80 Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 5 Connecting the Kinetix 6000 Drive System
Figure 38 - Grounded (B-Phase) Power Configuration (Delta Secondary)
The IAM module has a factory-installed ground jumper configured for grounded
power distribution.
Refer to Power Wiring Examples beginning on page 201
for input power
interconnect diagrams with and without the LIM module.
L3
L1
L2
DC-
DC+
L3
L2
L1
CONT EN-
CONT EN+
W
V
U
MBRK -
MBRK +
COM
PWR
DBRK -
DBRK +
CTRL 2
CTRL 1
1 2 3 4
1 2 3 4 5 6
1 2
1 2 3 4 5 6
1 2
BAUD
RATE
TX
RX
DPI
1 2 3 4 5 6 7 8 9
Transformer (Delta) Secondary
Bonded Cabinet
Ground
Transformer
Ground Grid or
Power Distribution Ground
Kinetix 6000 IAM Module,
Top View
Connect to power rail ground stud.
Three-phase
AC Line Filter
Input Fusing
M1
Contactor
IMPORTANT
If you determine that you have grounded power distribution in your plant,
you do not need to modify your IAM module.