86 Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 5 Connecting the Kinetix 6000 Drive System
Figure 41 - Setting the Ground Jumper (230V Series-A IAM modules)
P17
P16
P15
Top Screw
2094-ACxx-Mxx-x
IAM Module (230V)
Bottom Screw
Front Panel (opened)
Ground jumper set
for grounded configuration
(default setting).
Ground jumper set
for ungrounded configuration.
IMPORTANT
Use the default jumper setting or remove the jumper entirely for
grounded power configurations. Move the jumper, as shown above, for
ungrounded power.