EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-701 - Table 7.6; Thermal Element Expected Trip Times

Schweitzer Engineering Laboratories SEL-701
468 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
701 Motor Protection Relay Date Code 20010719
Commissioning
Selected Functional Tests
7.14
NOTE: Changing settings requires that you enter the Access
Level 2 password. The factory password is 701.
Step 3. Set the current source phase angles to apply balanced three-phase
currents. Refer to Figure 7.1 on page 7.4 for the correct angles, which
depend on the PHROT setting.
Step 4. Reset the motor thermal element using the front-panel Reset Thermal
Model function.
NOTE: This function requires that you enter the Access Level 2
password. The factory password is 701.
Set the current sources to apply the test current shown in Table 7.6,
then turn on the current sources together. Refer back to Table 7 .6 to
determine the expected element operating time. For instance, when
the setting CURVE is equal to 4, the thermal element should trip in
410 = 40 seconds when applied three-phase current equals three
times the motor full load current setting, FLA. Use the front-panel
Meter Values\Thermal & RTD Data function to view the estimated
Time to Thermal Trip during each test.
NOTE: Reset the motor thermal model before each test run or
the element will trip faster than expected.
Table 7.6 Th erma l Element Ex pected Trip Times
Table 7.6 Thermal Element Expected Trip Times
Applied
Current (A secondary)
Expected Time to Trip (s)
Measured Time to Trip (s)
1.2 FLA CURVE 145.7
1.5 FLA CURVE 51.5
2.0 FLA CURVE 23.3
3.0 FLA CURVE 10.0
4.0 FLA CURVE 5.63
5.0 FLA CURVE 3.60
6.0 FLA CURVE 2.50
7.0 FLA CURVE 1.84

Table of Contents

Related product manuals