Date Code 20010719 701 Motor Protection Relay
Settings Calculation
RTD-Based Protection
4.31
RTD Location Settings
Table 4.23 RTD L ocation Settings
The relay allows you to define the location of each monitored RTD independently
using the RTD Location settings.
Define the RTD Location settings using the following suggestions:
If an RTD is not connected to an input or has failed in place and will
not be replaced, set RTD Location for that input equal to NONE.
For RTDs embedded in motor stator windings, set RTD Location
equal to WDG.
For inputs connected to RTDs measuring bearing race temperature,
set RTD Location equal to BRG.
For the input connected to an RTD measuring ambient motor cooling
air temperature, set RTD Location equal to AMB. Only one ambient
temperature RTD is allowed.
For inputs connected to monitor temperatures of other apparatus, set
RTD Location equal to OTH.
Table 4.23 RTD Location Settings
Setting Prompt
Setting Range
Setting Name =
Factory Default
RTD Location WDG, BRG, AMB, OTH, NONE RTD1LOC = BRG
RTD Location WDG, BRG, AMB, OTH, NONE RTD2LOC = BRG
RTD Location WDG, BRG, AMB, OTH, NONE RTD3LOC = BRG
RTD Location WDG, BRG, AMB, OTH, NONE RTD4LOC = BRG
RTD Location WDG, BRG, AMB, OTH, NONE RTD5LOC = WDG
RTD Location WDG, BRG, AMB, OTH, NONE RTD6LOC = WDG
RTD Location WDG, BRG, AMB, OTH, NONE RTD7LOC = WDG
RTD Location WDG, BRG, AMB, OTH, NONE RTD8LOC = WDG
RTD Location WDG, BRG, AMB, OTH, NONE RTD9LOC = WDG
RTD Location WDG, BRG, AMB, OTH, NONE RTD10LOC = WDG
RTD Location WDG, BRG, AMB, OTH, NONE RTD11LOC = AMB
RTD Location
a
WDG, BRG, AMB, OTH, NONE RTD12LOC = OTH
a
The twelfth RTD input is only available when you use the SEL-2600 RTD Module.