Date Code 20010719 701 Motor Protection Relay
Metering & Monitoring
Motor Start Report
8.13
Executing the MSR F command does not affect the statistical data stored by the relay.
Figure 8.4 shows data from an example Motor Start Report.
=>msr
SEL-701 Date: 07/21/1999 Time: 17:13:04.295
MOTOR RELAY
FID=SEL-701-R102-V11xxx-Z000000-D19990702 CID=DE83
Date of Motor Start: 07/20/1999
Time of Motor Start: 13:59:28.618
Starts Since Last Reset: 7
Acceleration Time (s): 8.0
Starting % Thermal Capacity: 72
Maximum Starting Current (A pri): 3001
Minimum Starting Voltage (V pri): 4702
Cycle,Ia (A pri),Ib (A pri),Ic (A pri),In (A pri),Vab (V pri),Vbc (V pri),Vca (V pri),% Thermal
Capacity
5,2999,2994,2990,0,4705,4706,4705,17
10,2999,2993,2990,0,4708,4710,4707,18
15,2999,2993,2989,0,4702,4706,4704,18
20,3000,2993,2989,0,4708,4710,4707,19
.
.
.
470,2884,2882,2880,0,4720,4718,4716,71
475,2878,2880,2878,0,4719,4716,4718,71
480,1017,1008,988,0,4750,4752,4754,72
485,348,350,347,0,4780,4782,4784,72
490,348,349,347,0,4782,4782,4784,72
.
.
.
3595,347,348,347,0,4782,4784,4782,70
3600,348,348,348,0,4780,4782,4784,70
Figure 8.4 Motor Start Report Example.