701 Motor Protection Relay Date Code 20010719
SEL-2020/2030 & SEL-701PC Compatibility Features
Fast Binary Message Definitions
D.14
A5CE Fast Operate Configuration Block
In response to the A5CE request, the relay sends the block shown in Table D.8.
Table D.8 A5C E Fast Operat e Configuration B lock
Table D.8 A5CE Fast Operate Configuration Block
Data Description
A5CE Command
18 Length
01 Support 1 circuit breaker or contactor
0004 Support 4 remote bit set/clear commands
0100 Allow remote bit pulse commands
31 Operate code, open breaker/contactor (STOP)
11 Operate code, close breaker/contactor (STR)
00 Operate code, clear remote bit RB1
20 Operate code, set remote bit RB1
40 Operate code, pulse remote bit RB1
01 Operate code, clear remote bit RB2
21 Operate code, set remote bit RB2
41 Operate code, pulse remote bit RB2
02 Operate code, clear remote bit RB3
22 Operate code, set remote bit RB3
42 Operate code, pulse remote bit RB3
03 Operate code, clear remote bit RB4
23 Operate code, set remote bit RB4
43 Operate code, pulse remote bit RB4
00 Reserved
checksum 1-byte checksum of all preceding bytes