Date Code 20010719 701 Motor Protection Relay
SEL-2020/2030 & SEL-701PC Compatibility Features
Fast Binary Message Definitions
D.3
Fast Binary Message Definitions
A5C0 Relay Definition Block
In response to the A5C0 request, the relay sends the block shown in Table D .3 .
Table D.3 A5C 0 Relay Definit ion Block
Table D.3 A5C0 Relay Definition Block
Data Description
A5C0 Command
48 Length
02 Support two protocols
03 Support three Fast Meter messages
06 Support three status flag commands
A5C1 Fast Meter configuration command
A5D1 Fast Meter command
A5C2 Demand Fast Meter configuration command
A5D2 Demand Fast Meter command
A5C3 Peak Demand Fast Meter configuration command
A5D3 Peak Demand Fast Meter command
0004 Settings change bit
A5C100000000 Fast Meter configuration message
0004 Settings change bit
A5C200000000 Demand Fast Meter configuration message
0004 Settings change bit
A5C300000000 Peak Demand Fast Meter configuration message
0004 Settings change bit
444E410D0000 DNA Command
0004 Settings change bit
49440D000000 ID Command
0004 Settings change bit
4341530D0000 CAS Command
0100 SEL protocol, Fast Operate
0002 Modbus protocol
00 Reserved
checksum 1-byte checksum of preceding bytes