Date Code 20010719 701 Motor Protection Relay
Date ___________
Created by ___________
Factory Defaults
Appendix F
SEL-701 Relay Settings Sheets
RELAY SETTINGS (Factory Defaults, Model 070101X)
General Data
Relay Identifier
Range: 20 Characters RID = SEL-701
Terminal Identifier
Range: 20 Characters TID = MOTOR RELAY
Phase (IA, IB, IC) CT Ratio
Range: 1-6000 CTR = 100
Phase CT Secondary Rating
Range: 1 A, 5 A ITAP = 5
Neutral (IN) CT Ratio
Range: 1-6000 CTRN = 100
Neutral CT Secondary Rating
Range: 1 A, 5 A INTAP = 5
Phase Rotation
Range: ABC, ACB PHROT = ABC
Nominal Frequency
Range: 50, 60 Hz FNOM = 60
Date Format
Range: MDY, YMD DATE_F = MDY
Demand Meter Time Constant
Range: 5, 10, 15, 30, 60 min DTMC = 15
Phase (VA, VB, VC) VT Ratio
(Hidden if voltages not included)
Range: 1-6000 PTR = 100
Phase VT Connection
(Hidden if voltages not included)
Range: D, Y DELTA_Y = Y
Single Voltage Input
(Hidden if voltages not included)
Range: Y, N SINGLEV = N