EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-734 - Figure 8.12 SEL OGIC Variable SV10 Timing Logic

Schweitzer Engineering Laboratories SEL-734
344 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.12
SEL-734 Meter Instruction Manual Date Code 20090730
Logic
Counter Variables
Example 8.2 illustrates how to use the SELOGIC control equation counters to
limit the demand by starting an on-site diesel generator.
EXAMPLE 8.2 Using Counters to Control Generator Starting via
Load Monitoring
When the three-phase demand is greater than 100 kW for greater
than 10 minutes, the diesel generator should start to pick up demand.
The generator should be started in 5 minutes when demand is > 125
kW. Also, if the demand is greater than 150 kW, the diesel generator
should start immediately. In order to achieve this function, make the
following settings:
ESC := 1
ESV := 10
SC01PV := 60
SC01R := IN401
# disable the starting of the generator if desired
SC01LD := IN402 OR (MW3DI > 150) # start the generator
immediately
SV10 := NOT(SV10T) # 10 second period
SC01CU := R_TRIG SV10 AND (MW3DI > 100) OR
F_TRIG SV10 AND (MW3DI > 125)
# increment counter SC01,
faster when the demand is higher than 125.00
SC01CD := R_TRIG SV10 AND (MW3DI < 100) # decrement counter
SC01 when the demand is below 100.00
OUT402 := (SC01 > 48) # warning that diesel generator is about to
start
OUT401 := SC01QU # start generator signal
Figure 8.12 SEL
OGIC Variable SV10 Timing Logic
Because demands are slow changing values, it does not make sense to check
them continuously. The ten-second period on SV10T makes the preset value
setting easier to determine.
Figure 8.13 is provided as a reference to this example.
SCnQU Output, Word Bit This word bit output asserts when SCn = SCnPV.
SCnQD Output, Word Bit This word bit asserts when SCn = 0.
SCn Output, Analog
Va lu e
Present counter value. Use with any analog compari-
son in SEL
OGIC and view using the COU command.
Table 8.3 Counter Inputs and Outputs (Sheet 2 of 2)
Name Type Description
NOTE: SCn is stored in volatile
memory and is lost when the meter
loses power.
SV10
SV10T
5.00
5.00
Preset Value
10 minutes 60 s/minute
10 x/count
------------------------------------------------------------- 60 s/count==
Courtesy of NationalSwitchgear.com

Table of Contents

Other manuals for Schweitzer Engineering Laboratories SEL-734