EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-734 - Table H.1 Instantaneous and RMS Quantities

Schweitzer Engineering Laboratories SEL-734
344 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H.2
SEL-734 Meter Instruction Manual Date Code 20090730
Analog Quantities
Table H.1 Instantaneous and RMS Quantities (Sheet 1 of 3)
Name Description Units
Usage
MET
(Pri)
HMI
(Pri)
LDP
(Sec)
DP
(Pri)
Logic
(Sec)
DNP
(Pri)
Modbus
(Sec)
FM
(Pri)
AO
(Pri)
Ix_MAG Current, x-phase, mag. where
x = A, B, C, or N
Amps
xxxxxx x xx
Ix_ANG Current, x-phase, ang. where
x = A, B, C, or N
degrees
xx xxx x xx
Ix_RMS Current, x-phase RMS mag. where
x = A, B, C, or N
Amps
xxxxxx x x
IG_MAG Current, neutral or calculated-
residual (auto switching), mag.
Amps
xxxx x x x
IG_ANG Current, neutral or calculated-
residual (auto switching), ang.
degrees
xx xx x x
I1_MAG Current, positive-seq., mag. Amps
xxxxxx x xx
I1_ANG Current, positive-seq., ang. degrees
xx xxx x xx
3I0_MAG Current, 3-phase zero-seq., mag. Amps
xx x x
3I0_ANG Current, 3-phase zero-seq., ang. degrees
xx x x
3I2_MAG Current, 3-phase neg.-seq., mag. Amps
xxxxxx x xx
3I2_ANG Current, 3-phase neg.-seq., ang. degrees
xx xxx x xx
Vx_MAG (9) Voltage, x-phase-to-neutral mag.
where x = A, B, C, or N
Volts
xxxxxx x xx
Vx_ANG (9) Voltage, x-phase, ang.where
x = A, B, C, or N
degrees
xx xxx x xx
Vx_RMS (9) Voltage, x-phase RMS mag. where
x = A, B, C, or N
Volts
xxxxxx x x
Vx_MAG Voltage, x-phase mag. where
x = AB, BC, or CA
Volts
xxxxxx x
a
xx
Vx_ANG Voltage, x-phase, ang. where
x = AB, BC, or CA
degrees
xx xxx x
a
xx
Vx_RMS Voltage, x RMS mag. where
x = AB, BC, or CA
Volts
xxxxxx x
a
x
V1_MAG Voltage, positive-seq. mag. Volts
xxxxxx x xx
V1_ANG Voltage, positive-seq., ang. degrees
xx xxx x xx
V2_MAG Voltage, neg.-seq., Y-terminals, mag. Volts
xxxxxx x xx
V2_ANG Voltage, neg.-seq., ang. degrees
xx xxx x xx
3V0_MAG (9) Voltage, 3-phase zero-seq. mag. Volts
xxxxxx x xx
3V0_ANG (9) Voltage, 3-phase zero-seq., ang. degrees
xx xxx x xx
MWx (9) Real power mag., x-phase where
x = A, B, or C
Watts
xxxx x
xx
MW3 Real power magnitude, 3-phase Watts
xxxx x
xx
MWx_AVG (9) Real power RMS mag., x-phase where
x = A, B, or C
Watts
xxxxxx x x
MW3_AVG Real power RMS magnitude, 3-phase Watts
xxxxxx x x
MVRx(9) Reactive power mag., x-phase where
x = A, B, or C
VA R x x x x x x
Courtesy of NationalSwitchgear.com