F.21
Date Code 20090730 Instruction Manual SEL-734 Meter
Modbus RTU Communications Protocol
Modbus RTU Communications Protocol
1991 07C7 VA CF Max, Crest Factor UINT100
1992–1997 07C8–07CD VA CF Max Time and Date UINT
1998 07CE VB CF Min, Crest Factor VBC CF if Form 5 UINT100
1999–2004 07CF–07D4 VB CF Min Time and Date UINT
2005 07D5 VB CF Max, Crest Factor UINT100
2006–2011 07D6–07DB VB CF Max Time and Date UINT
2012 07DC VC CF Min, Crest Factor VCA CF if Form 5 UINT100
2013–2018 07DD07E2 VC CF Min Time and Date UINT
2019 07E3 VC CF Max, Crest Factor UINT100
2020–2025 07E4–07E9 VC CF Max Time and Date UINT
2026 07EA MW3P CF Max Power UINT100
2027–2032 07EB–07F0 MW3P CF Max Power Time and Date UINT
2033 07F1 MW3P CF Min Power UINT100
2034–2039 07F2–07F7 MW3P CF Min Power Time and Date UINT
2040 07F8 MVAR3P CF Max Power UINT100
2041–2046 07F9–07FE MVAR3P CF Max Power Time and Date UINT
2047 07FF MVAR3P CF Min Power UINT100
2048–2053 0800–0805 MVAR3P CF Min Power Time and Date UINT
2054–2059 0806–080B CF Last Reset Time and Date UINT
2060–2175 080C–087F Reserved
Transformer Line Loss
Metering
Analog values are in secondary.
21762181 08800885 Supply Line Loss A, B, C (W) Reserved if Form 5 LONG100
21822183 08860887 Supply Line Loss 3P (W) LONG100
21842189 0888088D Supply Line Loss A, B, C (VAR) Reserved if Form 5 LONG100
21902191 088E–088F Supply Line Loss 3P (VAR) LONG100
21922197 08900895 Load Line Loss A, B, C (W) Reserved if Form 5 LONG100
21982199 08960897 Load Line Loss 3P (W) LONG100
22002205 0898089D Load Line Loss A, B, C (VAR) Reserved if Form 5 LONG100
22062207 089E–089F Load Line Loss 3P (VAR) LONG100
22082213 08A008A5 CU Watt Loss A, B, C (W) Reserved if Form 5 LONG100
22142215 08A608A7 CU Watt Loss 3P (W) LONG100
22162221 08A808AD CU VAR Loss A, B, C (VAR) Reserved if Form 5 LONG100
22222223 08AE–08AF CU VAR Loss 3P (VAR) LONG100
22242229 08B008B5 FE Watt Loss A, B, C (W) Reserved if Form 5 LONG100
22302231 08B608B7 FE Watt Loss 3P (W) LONG100
22322237 08B808BD FE VAR Loss A, B, C (VAR) Reserved if Form 5 LONG100
22382239 08BE–08BF FE VAR Loss 3P (VAR) LONG100
22402245 08C008C5 Transformer Loss A, B, C (VA) Reserved if Form 5 LONG100
22462247 08C608C7 Transformer Loss 3P (VA) LONG100
2248–2303 08C8–08FF Reserved
Table F.23 Modbus Register Map (Sheet 11 of 19)