Article number without filter
Article number with filter
6SL3210-1RH31-4UL0
6SL3210-1RH31-4AL0
HO base load input current 122 A
HO base load output current 115 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1225-0 / 200 A
200 A
Power loss without filter 2.56 kW
Power loss with filter 2.59 kW
Required cooling air flow 153 l/s
Weight without filter 60 kg
Weight with filter 64 kg
Technical data
10.4 Technical Data, PM240P-2 Power Module
Converter with the CU230P-2 Control Units
462 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE