Technical Specifications
7-99
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Standard temperature range, Pt 100
In the following table you will find the representation of the digitized measured
value for the standard temperature range of the Pt 100 sensor. The characteristic
linearization applies to the following temperature ranges: 200 C to + 850 C (in
increments of 0.5 C).
Table 7-55 SIMATIC S5 format: representation of the digitized measured value for the standard
temperature range, Pt 100 (expansion module with analog inputs)
Measured Units Data word Range
value
in C
(dec.)
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
x F Ü
1000.0 2001 0 0 1 1 1 1 1 0 1 0 0 0 1 0 0 1 Overflow
1000.0 2000 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0 0 Over-
851.0 1702 0 0 1 1 0 1 0 1 0 0 1 1 0 0 0 0
range*
850.0 1700 0 0 1 1 0 1 0 1 0 0 1 0 0 0 0 0
100 200 0 0 0 0 0 1 1001000000
0.0 0 0 0 0 0 0 0 000000000 0 Rated
20 40 1 1 1 1 1 1 1011000000
range
100.0 200 1 1 1 1 1 0 0111000000
101.0 202 1 1 1 1 1 0 0 1 1 0 1 1 0 0 0 0 Under-
243.0 486 1 1 1 1 0 0 0 0 1 1 0 1 0 0 0 0
range
243.0 487 1 1 1 1 0 0 0 0 1 1 0 0 1 0 0 1 Under-
flow*
* In the overrange and underrange, the gradient of the characteristic curve at the point where the linearized rated range is
left is retained.