EasyManua.ls Logo

Siemens SIPROTEC 4 7UT6 Series - Page 323

Siemens SIPROTEC 4 7UT6 Series
684 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Jumper Rated voltage
DC 24 V to 48 V DC 60 V to 125 V DC 110 V to 250 V,
AC 115 V to 230 V
DC 220 V to 250 V,
AC 115 V to 230 V
X55 not used not used 1-2 1-2
cannot be changed interchangeable
Fuse T4H250V T2H250V
Table 3-6 Jumper setting of the Pickup Voltages of the binary inputs BI1 to BI5 on the C-CPU-2
processor module
Binary Inputs Jumper
Threshold 19 V
1)
Threshold 88 V
2)
Threshold 176 V
3)
BI1 X21 1-2 2-3 3-4
BI2 X22 1-2 2-3 3-4
BI3 X23 1-2 2-3 3-4
BI4 X24 1-2 2-3 3-4
BI5 X25 1-2 2-3 3-4
1)
Factory settings for devices with rated power supply voltage DC 24 to 125 V
2)
Factory settings for devices with rated power supply voltage DC 110 to 220 V, AC 115 to 230 V to 250 V
3)
Only for control voltage DC 200 V or DC 250 V
Table 3-7 Jumper setting of the quiescent state of the Life Contact on the processor board C-CPU-2
Jumper Open in the quiescent state Closed in the quiescent state Presetting
X40 1-2 2-3 2-3
By repositioning jumpers the interface RS485 can be modified into a RS232 interface and vice versa.
Jumpers X105 to X110 must be set to the same position!
Table 3-8
Jumper settings of the integrated RS232/RS485 Interface on the C-CPU-2 processor board
Jumper RS232 RS485
X103 and X104 1-2 1-2
X105 to X110 1-2 2-3
The jumpers are preset at the factory according to the configuration ordered.
With interface RS232 jumper X111 is needed to activate CTS which enables the communication with the
modem.
Table 3-9
Jumper setting for CTS (Clear To Send, flow control) on the C-CPU-2 processor board
Jumper /CTS from interface RS232 /CTS triggered by /RTS
X111 1-2
2-3
1)
1)
Delivery state
Jumper setting 2-3: The connection to the modem is usually established with a star coupler or fibre-optic
converter. Therefore the modem control signals according to RS232 standard DIN 66020 are not available.
Modem signals are not required since the connection to the SIPROTEC 4 devices is always operated in the half-
duplex mode. Please use the connection cable with order number 7XV5100-4.
Jumper setting 1-2: This setting makes the modem signals available, i. e. for a direct RS232-connection
between the SIPROTEC 4 device and the modem this setting can be selected optionally. We recommend to use
a standard RS232 modem connection cable (converter 9-pin to 25-pin).
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7UT6x, Manual 323
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Related product manuals