Message No. Meaning see
Section
O/L2 Adap.fact. 204.2494 The matching factor of the current transformers for overload protec-
tion 2 is too great or too small
2.9 Thermal
Overload
Protection
U/f Not avail.
5377 Overexcitation protection is not available for the configured protected
object
2.1.4 Power
System Data
1
U/f Err No VT
5376 Overexcitation protection is not available without voltage connection 2.1.4 Power
System Data
1
U/f err. Set.
5378 Overexcitation protection setting not plausible 2.11 Over-
excitation
Protection
U< err. Obj. 033.2491 Undervoltage protection is not available for the configured protected
object
2.14 Under-
voltage
Protection
U< err. VT 033.2492 Undervoltage protection is not available without voltage connection 2.14 Under-
voltage
Protection
U> err. Obj. 034.2491 Overvoltage protection is not available for the configured protected
object
2.15 Over-
voltage
Protection
U> err. VT 034.2492 Overvoltage protection is not available without voltage connection 2.15 Over-
voltage
Protection
Freq. err.
Obj.
5255 Frequency protection is not available for the configured protected
object
2.16 Freque
ncy Protec-
tion
Freq. error VT
5254 Frequency protection is not available without voltage connection 2.16 Freque
ncy Protec-
tion
Freq. err.
Set.
5256 Frequency protection setting not plausible 2.16 Freque
ncy Protec-
tion
Pr obj. error
5101 Reverse power protection is not available for the configured protected
object
2.12 Reverse
Power
Protection
Pr CT Fact ><
5099 The matching factor of the current transformers for reverse power
protection is too great or too small.
2.12 Reverse
Power
Protection
Pr VT error
5100 Reverse power protection is not available without voltage connection 2.12 Reverse
Power
Protection
Pr set error
5102 Reverse power protection setting not plausible 2.12 Reverse
Power
Protection
Pf> Object err
5132 Forward power supervision is not available for the configured
protected object
2.13 Forwar
d Power
Supervision
Pf> CT fact ><
5130 The matching factor of the current transformers for forward power
supervision is too great or too small.
2.13 Forwar
d Power
Supervision
Mounting and Commissioning
3.3 Commissioning
SIPROTEC 4, 7UT6x, Manual 363
C53000-G1176-C230-5, Edition 09.2016