Addr. Parameter Function C Setting Options Default Setting Comments
470 BREAKER FAIL.AT P.System Data
1
Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Ext. switchg. 1
Side 1 Breaker Failure Protection
assigned to
471 BREAKER FAIL2AT P.System Data
1
Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Ext. switchg. 1
Side 1 Breaker Failure Protection
2 assigned to
511 STRPNT->OBJ M1 P.System Data
1
YES
NO
YES CT-Strpnt. Meas. Loc.1 in
Dir. of Object
512 IN-PRI CT M1 P.System Data
1
1 .. 100000 A 200 A CT Rated Primary Current
Meas. Loc. 1
513 IN-SEC CT M1 P.System Data
1
1A
5A
1A CT Rated Secondary
Current Meas. Loc. 1
521 STRPNT->OBJ M2 P.System Data
1
YES
NO
YES CT-Strpnt. Meas. Loc.2 in
Dir. of Object
522 IN-PRI CT M2 P.System Data
1
1 .. 100000 A 2000 A CT Rated Primary Current
Meas. Loc. 2
523 IN-SEC CT M2 P.System Data
1
1A
5A
1A CT Rated Secondary
Current Meas. Loc. 2
531 STRPNT->OBJ M3 P.System Data
1
YES
NO
YES CT-Strpnt. Meas. Loc.3 in
Dir. of Object
532 IN-PRI CT M3 P.System Data
1
1 .. 100000 A 2000 A CT Rated Primary Current
Meas. Loc. 3
533 IN-SEC CT M3 P.System Data
1
1A
5A
1A CT Rated Secondary
Current Meas. Loc. 3
541 STRPNT->OBJ M4 P.System Data
1
YES
NO
YES CT-Strpnt. Meas. Loc.4 in
Dir. of Object
542 IN-PRI CT M4 P.System Data
1
1 .. 100000 A 2000 A CT Rated Primary Current
Meas. Loc. 4
543 IN-SEC CT M4 P.System Data
1
1A
5A
1A CT Rated Secondary
Current Meas. Loc. 4
551 STRPNT->OBJ M5 P.System Data
1
YES
NO
YES CT-Strpnt. Meas. Loc.5 in
Dir. of Object
Functions, Settings, Information
F.2 Settings
556 SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016

Table of Contents