Addr. Parameter Function C Setting Options Default Setting Comments
552 IN-PRI CT M5 P.System Data
1
1 .. 100000 A 2000 A CT Rated Primary Current
Meas. Loc. 5
553 IN-SEC CT M5 P.System Data
1
1A
5A
1A CT Rated Secondary
Current Meas. Loc. 5
561 STRPNT->BUS I1 P.System Data
1
YES
NO
YES CT-Starpoint I1 in Direc-
tion of Busbar
562 IN-PRI CT I1 P.System Data
1
1 .. 100000 A 200 A CT Rated Primary Current
I1
563 IN-SEC CT I1 P.System Data
1
1A
5A
0.1A
1A CT Rated Secondary
Current I1
571 STRPNT->BUS I2 P.System Data
1
YES
NO
YES CT-Starpoint I2 in Direc-
tion of Busbar
572 IN-PRI CT I2 P.System Data
1
1 .. 100000 A 200 A CT Rated Primary Current
I2
573 IN-SEC CT I2 P.System Data
1
1A
5A
0.1A
1A CT Rated Secondary
Current I2
581 STRPNT->BUS I3 P.System Data
1
YES
NO
YES CT-Starpoint I3 in Direc-
tion of Busbar
582 IN-PRI CT I3 P.System Data
1
1 .. 100000 A 200 A CT Rated Primary Current
I3
583 IN-SEC CT I3 P.System Data
1
1A
5A
0.1A
1A CT Rated Secondary
Current I3
591 STRPNT->BUS I4 P.System Data
1
YES
NO
YES CT-Starpoint I4 in Direc-
tion of Busbar
592 IN-PRI CT I4 P.System Data
1
1 .. 100000 A 200 A CT Rated Primary Current
I4
593 IN-SEC CT I4 P.System Data
1
1A
5A
0.1A
1A CT Rated Secondary
Current I4
601 STRPNT->BUS I5 P.System Data
1
YES
NO
YES CT-Starpoint I5 in Direc-
tion of Busbar
602 IN-PRI CT I5 P.System Data
1
1 .. 100000 A 200 A CT Rated Primary Current
I5
603 IN-SEC CT I5 P.System Data
1
1A
5A
0.1A
1A CT Rated Secondary
Current I5
611 STRPNT->BUS I6 P.System Data
1
YES
NO
YES CT-Starpoint I6 in Direc-
tion of Busbar
612 IN-PRI CT I6 P.System Data
1
1 .. 100000 A 200 A CT Rated Primary Current
I6
613 IN-SEC CT I6 P.System Data
1
1A
5A
0.1A
1A CT Rated Secondary
Current I6
621 STRPNT->BUS I7 P.System Data
1
YES
NO
YES CT-Starpoint I7 in Direc-
tion of Busbar
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7UT6x, Manual 557
C53000-G1176-C230-5, Edition 09.2016