Addr. Parameter Function C Setting Options Default Setting Comments
5316 T U>> Overvoltage 0.00 .. 60.00 sec; ∞ 0.50 sec T U>> Time Delay
5317A DOUT RATIO Overvoltage 0.90 .. 0.99 0.98 U>, U>> Drop Out Ratio
5318A VALUES Overvoltage U-ph-ph
U-ph-e
U-ph-ph Measurement Values
5601 O/U FREQUENCY Frequency Prot. OFF
ON
Block relay
OFF Over / Under Frequency
Protection
5611 f< Frequency Prot. 40.00 .. 49.99 Hz; 0 49.50 Hz Pick-up frequency f<
5612 f<< Frequency Prot. 40.00 .. 49.99 Hz; 0 48.00 Hz Pick-up frequency f<<
5613 f<<< Frequency Prot. 40.00 .. 49.99 Hz; 0 47.00 Hz Pick-up frequency f<<<
5614 f> Frequency Prot. 50.01 .. 66.00 Hz; ∞ 52.00 Hz Pick-up frequency f>
5621 f< Frequency Prot. 50.00 .. 59.99 Hz; 0 59.50 Hz Pick-up frequency f<
5622 f<< Frequency Prot. 50.00 .. 59.99 Hz; 0 58.00 Hz Pick-up frequency f<<
5623 f<<< Frequency Prot. 50.00 .. 59.99 Hz; 0 57.00 Hz Pick-up frequency f<<<
5624 f> Frequency Prot. 60.01 .. 66.00 Hz; ∞ 62.00 Hz Pick-up frequency f>
5631 f< Frequency Prot. 10.00 .. 16.69 Hz; 0 16.50 Hz Pick-up frequency f<
5632 f<< Frequency Prot. 10.00 .. 16.69 Hz; 0 16.00 Hz Pick-up frequency f<<
5633 f<<< Frequency Prot. 10.00 .. 16.69 Hz; 0 15.70 Hz Pick-up frequency f<<<
5634 f> Frequency Prot. 16.67 .. 22.00 Hz; ∞ 17.40 Hz Pick-up frequency f>
5641 T f< Frequency Prot. 0.00 .. 100.00 sec;
∞
20.00 sec Delay time T f<
5642 T f<< Frequency Prot. 0.00 .. 600.00 sec;
∞
1.00 sec Delay time T f<<
5643 T f<<< Frequency Prot. 0.00 .. 100.00 sec;
∞
6.00 sec Delay time T f<<<
5644 T f> Frequency Prot. 0.00 .. 100.00 sec;
∞
10.00 sec Delay time T f>
5651 Umin Frequency Prot. 10.0 .. 125.0 V; 0 65.0 V Minimum Required
Voltage for Operation
5652 U MIN Frequency Prot. 0.10 .. 1.25 U/UnS;
0
0.65 U/UnS Minimum voltage
7001 BREAKER FAILURE Breaker Failure OFF
ON
Block relay
OFF Breaker Failure Protection
7011 START WITH REL. Breaker Failure 0 .. 8 0 Start with Relay (intern)
7012 START WITH REL. Breaker Failure 0 .. 24 0 Start with Relay (intern)
7015 T1 Breaker Failure 0.00 .. 60.00 sec; ∞ 0.15 sec T1, Delay of 1st stage
(local trip)
7016 T2 Breaker Failure 0.00 .. 60.00 sec; ∞ 0.30 sec T2, Delay of 2nd stage
(busbar trip)
7101 BREAKER FAILURE Breaker Fail. 2 OFF
ON
Block relay
OFF Breaker Failure Protection
7111 START WITH REL. Breaker Fail. 2 0 .. 8 0 Start with Relay (intern)
7112 START WITH REL. Breaker Fail. 2 0 .. 24 0 Start with Relay (intern)
7115 T1 Breaker Fail. 2 0.00 .. 60.00 sec; ∞ 0.15 sec T1, Delay of 1st stage
(local trip)
7116 T2 Breaker Fail. 2 0.00 .. 60.00 sec; ∞ 0.30 sec T2, Delay of 2nd stage
(busbar trip)