Addr. Parameter Function C Setting Options Default Setting Comments
7601 POWER CALCUL. Measurement with V setting
with V measur.
with V setting Calculation of Power
7611 DMD Interval Demand meter 15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub Demand Calculation Inter-
vals
7612 DMD Sync.Time Demand meter On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour Demand Synchronization
Time
7621 MinMax cycRESET Min/Max meter NO
YES
YES Automatic Cyclic Reset
Function
7622 MiMa RESET TIME Min/Max meter 0 .. 1439 min 0 min MinMax Reset Timer
7623 MiMa RESETCYCLE Min/Max meter 1 .. 365 Days 7 Days MinMax Reset Cycle
Period
7624 MinMaxRES.START Min/Max meter 1 .. 365 Days 1 Days MinMax Start Reset Cycle
in
8101 BALANCE I Meas-
urem.Superv
ON
OFF
OFF Current Balance Supervi-
sion
8102 BALANCE U Meas-
urem.Superv
ON
OFF
OFF Voltage Balance Supervi-
sion
8104 SUMMATION U Meas-
urem.Superv
ON
OFF
OFF Voltage Summation
Supervision
8105 PHASE ROTAT. I Meas-
urem.Superv
ON
OFF
OFF Current Phase Rotation
Supervision
8106 PHASE ROTAT. U Meas-
urem.Superv
ON
OFF
OFF Voltage Phase Rotation
Supervision
8111 BAL. I LIMIT M1 Meas-
urem.Superv
1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 1
5A 0.50 .. 5.00 A 2.50 A
8112 BAL. FACT. I M1 Meas-
urem.Superv
0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.1
8113A T Sym. I th. M1 Meas-
urem.Superv
5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8121 BAL. I LIMIT M2 Meas-
urem.Superv
1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 2
5A 0.50 .. 5.00 A 2.50 A
8122 BAL. FACT. I M2 Meas-
urem.Superv
0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.2
8123A T Sym. I th. M2 Meas-
urem.Superv
5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8131 BAL. I LIMIT M3 Meas-
urem.Superv
1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 3
5A 0.50 .. 5.00 A 2.50 A
8132 BAL. FACT. I M3 Meas-
urem.Superv
0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.3
8133A T Sym. I th. M3 Meas-
urem.Superv
5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay