EasyManua.ls Logo

Siemens SIPROTEC 4 7UT6 Series - Page 94

Siemens SIPROTEC 4 7UT6 Series
684 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[diff-stromdefinition-020926-rei, 1, en_GB]
Figure 2-20 Definition of current direction
Through-flowing current under undisturbed conditions or external fault:
Ι
1
flows into the protected zone, Ι
2
leaves the protected zone, i.e. is negative according tot he definition
of signs, therefore
Ι
2
= –Ι
1
;
moreover |Ι
2
| = |Ι
1
|
Ι
diff
= |
Ι
1
+ Ι
2
| = |Ι
1
Ι
1
| = 0
Ι
stab
= |Ι
1
| + |Ι
2
| = |Ι
1
| + |Ι
1
| = 2 · |Ι
1
|
No tripping effect (Ι
diff
= 0); the stabilisation (Ι
stab
) corresponds to double the through-flowing current.
Internal short-circuit, e.g. fed with equal currents each side:
The following applies
Ι
2
= Ι
1
; außerdem ist |Ι
2
| = |Ι
1
|
Ι
diff
= |Ι
1
+ Ι
2
| = |Ι
1
+ Ι
1
| = 2 · |Ι
1
|
Ι
stab
= |Ι
1
| + |Ι
2
| = |Ι
1
| + |Ι
1
| = 2 · |Ι
1
|
Tripping effect (Ι
diff
) and restraint value (Ι
stab
) are equal and correspond to the total fault.
Internal short-circuit, fed from one side only:
The following applies Ι
2
= 0
Ι
diff
= |Ι
1
+ Ι
2
| = |Ι
1
+ 0| = |Ι
1
|
Ι
stab
= |Ι
1
| + |Ι
2
| = |Ι
1
| + 0 = |Ι
1
|
Tripping quantity (Ι
diff
) and restraint value (Ι
stab
) are equal and correspond to the single-sided fault
current.
This result shows that for internal fault Ι
diff
= Ι
stab
. Thus, the characteristic of internal faults is a straight line
with the slope 1 (45°) in the operation diagram (dash-dotted fault characteristic in Figure 2-21).
Functions
2.2 Differential Protection
94 SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Related product manuals