Figure 6-64 Directional zero voltage time protection with non-directional back-up stage
Phase Current
Stabilization
Non-symmetrical load conditions in multiple-earthed systems or different current
transformer errors can result in a zero sequence current. This zero sequence current
could cause faulty pick-up of the earth current stages if low pick-up thresholds are set.
To avoid this, the earth current stages are stabilized by the phase current: As the
phase currents increase, the pick up thresholds are increased (Figure 6-65). The
stabilization factor (=slope) may be changed by means of the parameter ,SK67$%
6ORSH(setting address , Subsection 6.5.2). It applies to all stages.
Figure 6-65 Phase current stabilization