EasyManua.ls Logo

Siemens siprotec 7SA6 - Page 328

Siemens siprotec 7SA6
792 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
6-146 7SA6 Manual
C53000-G1176-C133-1
Figure 6-86 Logic diagram of the stub protection
Switching onto a
Dead Fault
To achieve fast tripping following manual closure of the circuit breaker onto a dead
fault, the switch onto fault signal can be routed to the overcurrent protection. The
overcurrent protection can then trip three-pole without delay or with a reduced delay.
It can be determined via setting parameter for which stage(s) the rapid tripping
following closure on to a dead fault applies. (Refer also to the logic diagrams in Figure
6-83, 6-84 and 6-86, and Sub-section 6.1.3, margin “Circuit Breaker Status”).
Fault Detection and
Trip Logic
The fault detection signals of the individual phases (and earth) and the individual
stages are combined in such a manner that both the phase information as well as the
stage information of the picked up stages can be output. (Table 6-10).
In the case of the trip signals, the stage which resulted in the trip command is also
indicated. If the device has the option to trip single-pole, and this option has been
activated, the pole which has been tripped is also indicated during single-pole tripping
(refer also to Sub-section 6.20.4 Overall Tripping Logic of the Device).
I
L3
I
L2
I
L1
I
ph

&

7,SK678%
T0
&
1

Yes
No
,678%627)

Yes
No
,678%7HOHS%,
1
L3
L2
L1
3I
0
&
T0
&
1
E
 7,!678%

I
E
switch onto
fault
T0
 627)7LPH'(/$<
,SK!678%
,!678%
7131
>I-STUB ENABLE
7130
>BLOCK I-STUB
7110
>O/C InstTRIP
I-STUB Trip E
I-STUB Pickup E
I-STUB Trip L3
I-STUB Trip L2
I-STUB Trip L1
I-STUB Pickup L3
I-STUB Pickup L2
I-STUB Pickup L1

Table of Contents

Other manuals for Siemens siprotec 7SA6

Related product manuals