Appendix
B-6
1151 SYN.MAN.CL Power System Data
2
with Synchronism-check
without Synchronism-check
NO
without Synchronism-check Manual CLOSE COMMAND genera-
tion
1155 3pole coupling Power System Data
2
with Pickup
with Trip
with Trip 3 pole coupling
1156A Trip2phFlt Power System Data
2
3pole
1pole, leading phase
1pole, lagging phase
3pole Trip type with 2phase faults
1201 FCT Distance Distance protec-
tion, general set-
tings
ON
OFF
ON Distance protection is
1202 Minimum Iph> Distance protec-
tion, general set-
tings
0.10..4.00 A 0.10 A Phase Current threshold for dist.
meas.
1203 3I0> Threshold Distance protec-
tion, general set-
tings
0.05..4.00 A 0.10 A 3I0 threshold for neutral current pikkup
1204 3U0> Threshold Distance protec-
tion, general set-
tings
1..100 V; 5 V 3U0 threshold zero seq. voltage pikkup
1205 3U0> COMP/ISOL. Distance protec-
tion, general set-
tings
10..200 V 40 V 3U0> pickup (comp/ isol. star-point)
1206 T3I0 1PHAS Distance protec-
tion, general set-
tings
0.00..0.50 sec 0.04 sec Delay 1ph-faults (comp/isol. star-point)
1207A 3I0>/ Iphmax Distance protec-
tion, general set-
tings
0.05..0.30 0.10 3I0>-pickup-stabilisation (3I0> /Iph-
max)
1215 Paral.Line Comp Distance protec-
tion, general set-
tings
NO
YES
NO Mutual coupling parall.line compensa-
tion
1220 PHASE PREF.2phe Distance protec-
tion, general set-
tings
L3 (L1) acyclic
L1 (L3) acyclic
L2 (L1) acyclic
L1 (L2) acyclic
L3 (L2) acyclic
L2 (L3) acyclic
L3 (L1) cyclic
L1 (L3) cyclic
all loops
L3 (L1) acyclic Phase preference for 2ph-e faults
1221A 2Ph-E faults Distance protec-
tion, general set-
tings
block leading ph-e loop
block lagging ph-e loop
all loops
only phase-phase loops
only phase-earth loops
block leading ph-e loop Loop selection with 2Ph-E faults
1232 SOTF zone Distance protec-
tion, general set-
tings
with Pickup (non-directional)
with Zone Z1B
Inactive
Inactive Instantaneous trip after SwitchOnTo-
Fault
1241 R load (Ø-E) Distance protec-
tion, general set-
tings
0.10..250.00 Ohm; Ohm R load, minimum Load Impedance (ph-
e)
1242 ϕ load (Ø-E) Distance protec-
tion, general set-
tings
20..60 ° 45 ° PHI load, maximum Load Angle (ph-e)
1243 R load (Ø-Ø) Distance protec-
tion, general set-
tings
0.10..250.00 Ohm; Ohm R load, minimum Load Impedance (ph-
ph)
1244 ϕ load (Ø-Ø) Distance protec-
tion, general set-
tings
20..60 ° 45 ° PHI load, maximum Load Angle (ph-
ph)
Addr. Setting Title Function Setting Options Default Setting Comments

Table of Contents